J-Y(St)Yh 2x2x0,8
详细说明
J-Y(St)Yh 2x2x0,8Twisted pair cable used in Konnex building management networks. | ||||||||
DESCRIPTION | ||||||||
Manufactured according to according to KNX / EIB specification. | ||||||||
TECHNICAL SPECIFICATIONS | ||||||||
Conductor | Solid Bare copper | 0.80±0.01 mm (AWG20) | ||||||
Insulation | PVC | 1.43±0.05 mm | ||||||
Identification of pairs | ||||||||
1 pair | Red / Black | |||||||
2 pair | White / Yellow | |||||||
Separator | Pet foil | |||||||
Drain wire | Solid copper : 0.4 mm (AWG26) | |||||||
Shielding | Aluminum-polyester | |||||||
Sheath | PVC | |||||||
Color | Green (other option is available) | |||||||
Bending radius | ≥ 7,5 x Diameter (mm) Installation | |||||||
Storage temperature | -15℃—+70℃ | |||||||
Installation temperature | -10℃—+50℃ | |||||||
ELECTRICAL CHARACTERISTICS | ||||||||
Conductor Resistance | max. 73.2 | Ω/km | ||||||
Insulation Resistance | min. 100 | MΩx km | ||||||
Cap.conductor to conductor @ 800kHz | max. 100 | nF/km | ||||||
Cap.unbalance @ 800kHz | max. 300 | pF/100m | ||||||
Operating voltage | max. 300 | V | ||||||
Reaction to fire | Class Eca | |||||||
Appliance | ||||||||
Cable for use in bus systems (EIB - European Installaton Bus) and as ICA cable in power installations. Laying in/on plaster, even in moist and wet rooms. Not approved for power and underground installation. | ||||||||
Packing | ||||||||
| ||||||||
All sizes and values without tolerances are reference values. We reserves the right to amend this specification without prior notice. |